Set design, development, production, production and sales services as one of the diversified enterprises, the original high-end motor protector, successful research and development of intelligent integrated motor protector, motor protector, microcomputer protector, power meters, switchgear intelligent control device, service robot and other products.

-
Product Details
GY800 motor protection device

Product Introduction
GY800 motor protection device is indispensable protection device for the motor industry and the modern economy development, It is made by wide temperature and low power consumption 16 bit industrial smart integrated circuit, independent property right and software copyright. It can do the collection, calculation,analysis, measure &control,protection, alarming,monitor and interlock of the motor signal while the motor is functioning. Its use has almost penetrated into all fields and industries. It is an effective safety guarantee for the normal operation of three-phase motors used in industry, agriculture, national defense construction and people’s daily life. Therefore, it is of great significance to save energy, improve production efficiency , economic benefit and ensure safe production.
The new generation of intelligence has the functions of electricity calculation,accident analysis , motor error reporting and so on in addtion to conventional low-voltage motor protection, monitoring, control functions. Using the motor protect and control system to improve company’s reliability and safety will improve the company’s automatic management level for the functioning motors. GY800 motor protection device uses the LCD screen to display all the functioning motor’s datas like three-phase voltage,three-phase current,power factor,each time/total electricity,rate,power,error message,alarming value,total operating time and so on to complete the remote automatic control,direct control ,terminal control,forward and reverse stratup control,star triangle startup control,auto step-down control,direct bypass control to the motor。Its fieldbus RS5485 interfaces support various protocols which can be used in many microcomputer industrial control configuration software to complete the network communication management,on the other hand, it can also connect with the DCS system by the way of 4-20 Ma variable signal output, then transmit and output the operating parameters of the motor to form a distributed integrated electric power monitoring system to carry out a variety of control such as remote measurement&control,remote communication, remote control, protection, setting. GY800 motor protection device is designed with software,hardware and EMC self-calibration function, and has super anti-interference ability and the reliability of accurate and sensitive action.Its size is small and its structure is compact,so it can be straightly installed in Low voltage control terminal cabinet and each kind of 1/4 and above drawers by screw or lead rail,it is especially fit for scientific and effective industrial level protection and measure&protect module .
Function Summary
Protection Function |
Basic Functions |
Standard |
Match |
Remark |
overvoltage protection |
√ |
|
fuction after alarmed 3 seconds |
|
undervoltage protection |
√ |
|
fuction after alarmed 3 seconds(“0”stop fuction) |
|
overload protection |
√ |
|
current value&function time settable |
|
underload protection |
√ |
|
||
locked-rotor protection |
√ |
|
multiples of locked-rotor settable |
|
open-phase protection |
√ |
|
fuction after alarmed 3 seconds |
|
leakage protection |
√ |
|
set the value of the leakage current |
|
timeout protection |
√ |
|
start time delay setting according to the equipment need |
|
reversal protection |
|
√ |
function by automatic judgement |
|
feeder protection |
|
√ |
||
electric shock protection |
|
√ |
Automatic recovery within three seconds |
|
external fault protection |
|
√ |
function by automatic judgement |
|
electric delay protection |
√ |
|
delay time settable |
|
Control Function |
direct start-up |
√ |
|
select wiring according to the start mode, set the change-over time and start mode |
star triangulation start |
√ |
|
||
direct bypass start |
√ |
|
||
forward and reverse start |
√ |
|
||
step-down start |
√ |
|
||
Fault Reset |
manual reset |
√ |
|
time automatic reset or “0” shutoff to manual reset are selectable |
automatic reset |
√ |
|
||
Control Authority |
front-panel control |
√ |
|
set the control and protection rights |
remote terminal control |
√ |
|
||
fieldbus control |
√ |
|
||
Measure Function |
three-phase current |
√ |
|
monitor module |
three-phase voltage |
√ |
|
||
leakage current |
√ |
|
||
rate power |
|
√ |
||
power factor apparent power |
|
√ |
||
elctricity |
|
√ |
||
Communication Function |
RS485interfaces/ Mdobus-RTU |
|
√ |
protocol |
Analog Output |
One channel DC4-20mA |
|
√ |
internal DC24V power supply |
Switch Output |
6-channel optoelectronic barrier input,function editable |
|
√ |
|
Control Output |
6-channel relay output, function editable |
√ |
|
rivet capacity 5A |
Set Reminding |
full screen English |
√ |
|
LCD display |
Fault Query |
last ten fault query |
√ |
|
|
Time Query |
Accumulated or current time function time query |
√ |
|
|
Parameter Query |
function, set-up, fault message electric power, rate, apparent power |
√ |
|
Technical Parameter
Work power |
AC/DC 85~265V 50Hz |
|||
Power supply circuit voltage |
≤AC1160 |
|||
Control the relay output |
passive contact 5A |
|||
Install mode |
standard 35mm lead rail installation or screw fix |
|||
Field of application |
three-phase power supply equipment |
|||
Overvoltage protection |
set the voltage value |
110~465 V settable |
||
Undervoltage protection |
set the voltage value |
0~380V settable |
||
Overload protection |
current setting |
A settable within standard current |
||
function time |
1~255S settable |
|||
Underload protection |
current setting |
A settable within standard current |
||
function time |
0~255S settable |
|||
Open-phase protection |
percentage setting |
1~100% settable |
||
Leakage protection |
leakage current value setting |
50~5000mA settable |
||
function controlled by programming |
||||
Locked-rotor protection |
multiples setting |
1~9 multiples settable |
||
Timeout protection |
start delay time setting |
1~255S settable |
||
Fault reset |
manual reset |
be“0” |
||
automatic reset |
0~255S settable |
|||
20mA corresponding current |
set 20mA corresponding current value output |
|||
Communication address |
The device communication address |
1~255 machine settable |
||
Start type |
select start type |
direct startup, star triangle startup,forward and reverse startup, direct bypass,forward and reverse bypass startup,step-down startup settable |
||
Relay transfer time |
transfer time |
1~250S settable |
||
Programmable relay style |
startup delay close、leakage delay close、fault shutdown close、power on delay close、alarming delay close setable、low power factor alarming closed |
|||
Programmable relay output time |
output delay time |
1~250S settable |
||
Overload control protection |
when the motor is overload,the over current will be calculated according to the motor heat capacity tracking.Fully considered the motor rotor and stator’s temperature rise and the influence to the motor heating because of the three-phase unbalance.When the current reached the control protection value,the device will do the alarming and notice the shutdown delay time. |
|||
Underload protection |
when any one of the three-phase current is lower than the set underload value,the device will do the alarming and notice the shutdown delay time. |
|||
Locked-rotor protection |
when the current value reached the set current multiples,the protection device will do the alarming and notice the shutdown delay time. |
|||
Three-phase current unbalance protection |
when the ratio of the minimum phase or the maximum line current reaches or exceeds the set value, the protection device will do the alarming and notice the shutdown delay time. |
|||
Open-phase protection |
It will be judged as open-phase fault if any one of the three-phase current’s ratio is not bigger than the unbalanced angle value, the device will do the alarming and notice the shutdown delay time. |
|||
Overvoltage protection |
The protection device and the measure device monitor the three-phase voltage value, the device will do the alarming and notice the shutdown delay time if the equipment’s largest voltage is higher than the set value. |
|||
Undervoltage protection |
The protection device and the measure device monitor the three-phase voltage value, the device will do the alarming and notice the shutdown delay time if the equipment’s smallest voltage is lower than the set value. |
|||
Leakage (earth)protection |
Judge the leakage fault by using the zero sequence current transformer to measure the protective conductor(PE)or (PEN)’s short-circuit leakage current value.When the short-circuit leakage current value is bigger than the set leakage value, the device will do the alarming and notice the shutdown delay time. |
|||
Electric shock protection |
The protection device monitors the equipment’s voltage continuously, when the system voltage recovered after the moment dropped,the motor can start again. |
|||
Timeout protection |
The protection device inspects the start-up current delay time,when the equipment can bot be started up within the start-up delay time,and the three –phase current is 1.2 time bigger than set current,the timeout protection will function and the power will turn off. |
|||
Reversal protection |
When the protection device monitored the three-phase voltage sequence is not correct,the equipment can not start-up. |
|||
External fault protection |
When the device monitored the external switching value input signal is different from the device’s set switching value input signal,the device can not be started up. |
Current specification
Model |
Power range |
Current range |
remark |
6.3A |
0.55Kw-3.7Kw |
0.5A-6.3A |
Wring through the protection device CT hole directly |
20A |
3 Kw-12 Kw |
5A-20A |
|
63A |
10 Kw-30 Kw |
10A-63A |
|
100A |
20 Kw-50 Kw |
20A-100A |
|
150A |
37 Kw-90 Kw |
40A-160A |
|
300/5A |
75 Kw-132 Kw |
50A-300A |
Provide 3 pieces of turns ratio standard current tranformers |
400/5A |
90 Kw-200 Kw |
70A-400A |
|
600/5A |
110 Kw-300 Kw |
100A-600A |
|
800/5A |
155 Kw-400 Kw |
150A-800A |
|
1000/5A |
220 Kw-450 Kw |
250A-1000A |
|
1500/5A |
450 Kw-750 Kw |
400A-1500A |
Terminal definition(The terminal’s maximum linwidth is 1.5mm )
Terminal NO. |
Instruction |
1…2 |
Device working power AC/DC 220V input |
5…7 |
A/B/C three-phase voltage input |
4 |
N neutral point input |
35…36 |
Relay control J1 |
33…34 |
Relay control J2 |
31…32 |
Relay control J3 |
29…30 |
Protect the output relay J4 closing |
28…29 |
Protect the output relay J4 opening |
26…27 |
Programmable relay output J5 |
21…22 |
Zero-sequence current input |
3 |
Authority control or external fault |
15…16 |
4-20mA output(15 is - 16 is +) |
8 |
SDS stop input |
9 |
DCS start1 input |
10 |
DCS start2 input |
11…13 |
Equipment feedback input |
14 |
DC24V output value drive(Only for this device) |
23…24 |
RS485 communication interface(23isTA 24isTB) |
25 |
Device is earth |
18…20 |
|A-18/|B-19/|C-20Three-phase current input |
17 |
secondary current input common terminal |
Typical wiring

Installation size



Forward and reverse start control
In this mode,The device controls the relay 1 to make the motor forward and the relay 2 to make the motor backward.When the device received stop command or any protection action,it will transmit the stop command to the relay 1 and relay 2 to stop the motor function.

Direct start control
Direct start is the equipment’s basic start type.When the device received the fieldbus or“I/O” start signal, output relay’s contact point will control the 1 closed.When the device received stop or any protection signal,the contact point will control the 1 opened.

Direct bypass start control
When the device received the fieldbus or “I/O” start signal,the output control relay 1 will output a pulse closing signal.When the device received the stop or any protection signal,the output control relay 3 will output a pulse closing signal to open the direct bypass start mode,the operation screen will not work soon, and can start or stop the motor through the external button.

Star-triangle start control
The equipment is in star shape wiring before be started, When the start current is below 1/3 of the triangle shape wiring’s current and the start torque is also below 1/3 of the triangle shape wiring’s torque,the equipment will begin the star step-down start and will do the star-triangle transformation if reached the transformation time,Then it will function in triangle wiring mode.
Need to follow the principles when setting parameters:change-over time(start time,the star -triangle transformation must be completed before the equipment is started up).

Autotransformer step-down start control
As the name implies, the equipment is started through the autotansformer step-down.The reduction of the start voltage aims at reducing the start current,and the start torque will also reduce at the same time.
Need to follow the principles when setting parameters:change-over time(start time,the transformation must be completed before the equipment is started up).